Data sheet6ES7521-7BH00-0AB0

SIMATIC S7-1500, digital input module DI 16x24 V DC AUX; 16 channels in

groups of 8; for 24 V encoder; sensor supply 24 V DC; input type 2 (IEC 61131);

input delay parameterizable 0.05..20 ms; isochronous mode up to 250 µs;

integrated counting function up to 20 kHz; pulse stretching; chatter monitoring;

signal inversion diagnostics; hardware interrupts: front connector (screw terminals

or push-in) and, if applicable, order shield set separately

General information

Product type designation

HW functional status

Firmware version

● FW update possible

Product function

● I&M data

● Isochronous mode

● Prioritized startup

Engineering with

● STEP 7 TIA Portal configurable/integrated from version

● STEP 7 configurable/integrated from version

● PROFIBUS from GSD version/GSD revision

● PROFINET from GSD version/GSD revision

Operating mode

● DI

● Counter

● Oversampling

● MSI

Supply voltage

Rated value (DC)

permissible range, lower limit (DC)

permissible range, upper limit (DC)

Reverse polarity protection

Input current

Current consumption, max.

Encoder supply

Number of outputs

Short-circuit protection

24 V encoder supply

● 24 V

● Short-circuit protection

● Output current, max.

● Output current per module, max.

Power

Power available from the backplane bus

Power loss

Power loss, typ.

Digital inputs

Number of digital inputs16

7 W

0.6 W

Yes

Yes; Per group, electronic

150 mA; per group

300 mA

16; 2x 24 V DC

Yes

550 mA

24 V

19.2 V

28.8 V

Yes

Yes

Yes

Yes

Yes

STEP 7 V17 or higher

V5.5 SP3 / -

V1.0 / V5.1

V2.3 / -

Yes; I&M0 to I&M3

Yes

Yes

DI 16x24 V DC HS

From FS01

V1.0.0

Yes

6ES75217BH000AB0

Page 1/3

9/6/2023

Subject to change without notice

© Copyright Siemens

Digital inputs, parameterizable

Source/sink input

Input characteristic curve in accordance with IEC 61131, type 2

Pulse extension

Edge evaluation

Signal change flutter

Flutter observation window

Digital input functions, parameterizable

● Gate start/stop

● Freely usable digital input

● Counter

— Number, max.

— Counting frequency, max.

— Counting width

— Counting direction up/down

● Digital input with oversampling

— Number, max.

— Values per cycle, max.

— Resolution, min.

Input voltage

● Rated value (DC)

● for signal "0"

● for signal "1"

Input current

● for signal "1", typ.

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable

— at "0" to "1", min.

— at "0" to "1", max.

— at "1" to "0", min.

— at "1" to "0", max.

for interrupt inputs

— parameterizable

for technological functions

— parameterizable

Cable length

● shielded, max.

● unshielded, max.

Encoder

Connectable encoders

● 2-wire sensor

— permissible quiescent current (2-wire sensor), max.

Isochronous mode

Filtering and processing time (TCI), min.

Bus cycle time (TDP), min.

Interrupts/diagnostics/status information

Diagnostics function

Alarms

● Diagnostic alarm

● Hardware interrupt

Diagnoses

● Monitoring the supply voltage

● Monitoring of encoder power supply

● Wire-break

● Short-circuit

Diagnostics indication LED

● RUN LED

● ERROR LED

Yes

P-reading

Yes

Yes; 0.05 s, 0.1 s, 0.2 s, 0.5 s, 1 s, 2 s

Yes; Positive edge, negative edge

Yes; 2 to 32 signal changes

Yes; 0.5 s, 1 s to 100 s in 1-s steps

Yes; software/hardware gate

Yes

4; 4 totalizers max. 10 kHz or 2 totalizers max. 20 kHz + 2 totalizers max. 10

kHz

20 kHz

32 bit

Yes

Yes

16

16

15.625 µs

24 V

-30 to +5 V

+11 to +30V

9 mA

Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms

0.05 ms

20 ms

0.05 ms

20 ms

Yes

Yes

1 000 m; 600 m for technological functions; depending on input frequency,

encoder and cable quality; max. 50 m at 20 kHz

600 m; for technological functions: No

Yes

2 mA

60 µs; At 50 μs filter time

250 µs

Yes

Yes

Yes

Yes

Yes; short-circuit

Yes; to I < 350 µA

No

Yes; green LED

Yes; red LED

6ES75217BH000AB0

Page 2/3

9/6/2023

Subject to change without notice

© Copyright Siemens

● Monitoring of the supply voltage (PWR-LED)

● Channel status display

● for channel diagnostics

● for module diagnostics

Potential separation

Potential separation channels

● between the channels

● between the channels, in groups of

● between the channels and backplane bus

● Between the channels and load voltage L+

● between the channels and the power supply of the

electronics

Isolation

Isolation tested with

Standards, approvals, certificates

Suitable for safety functions

Ambient conditions

Ambient temperature during operation

● horizontal installation, min.

● horizontal installation, max.

● vertical installation, min.

● vertical installation, max.

Altitude during operation relating to sea level

● Installation altitude above sea level, max.

Dimensions

Width

Height

Depth

Weights

Weight, approx.

last modified:

Yes; green LED

Yes; green LED

Yes; red LED

Yes; red LED

No

8

Yes

Yes

No

707 V DC (type test)

No

-30 °C

60 °C

-30 °C

40 °C

5 000 m; Restrictions for installation altitudes > 2 000 m, see manual

35 mm

147 mm

129 mm

240 g

8/16/2023

6ES75217BH000AB0

Page 3/3

9/6/2023

Subject to change without notice

© Copyright Siemens