UPS报警详解
在使用UPS时会出现不同的报警,现将报警出现时的意义及处理方法进行说明如下:
(相序错)
A01?:
MAINS FAULT CYCLE DETECTION ERROR
POSTIL?: The R1 phase rotation is wrong.
注释:输入电源相序错误,更换任二相输入接点即可
(主电源故障)
A02?:
MAINS FAULT BATTERY IS DISCHARGING
POSTIL?: The R1 voltage is absent or out of tolerance.
注释:输入电源断电或超出允许范围,检查UPS 上游之输入开关是否跳脱,或于UPS 操
作面板上检查输入电压值是否异常;同时检查UPS的后备电池组是否处于放电状
态
(旁路电源故障)
A03?:
AUXILIARY MAINS FAULT
POSTIL: The auxiliary input mains voltage is absent, out of tolerance
注释:输入电压断电、超出规范或相序错误;报警出现的同时如果有A02报警同时存在时
表示外电网有问题,电池组正在放电。正常报警,检查外电网。
(过载机器即将关机)
A04?:
OVERLOAD IMMINENT SHUTDOWN
POSTIL: The power required by the load exceeds the power available via the UPS.
ATTENTION?: after the maximum overload time, the load is no longer powered.
注释:负载量大于UPS 之额定容量,请确认各相负载量不要大于UPS 各相之额定容量,
可于屏幕上检查各相之负载量并移除多余之负载。
注意:本UPS 具有过载承受能力,(过载能力(T°<30°C) 125%负载时,承受时间为10分
钟,150%过载时,承受时间为1分钟)当过载承受时间届满时,UPS 将停止供电。
(UPS故障)
A05?:
UPS FAULT
POSTIL: This is the UPS general alarm. This alarm is activated when at least one
alarm is present.
注释:此为UPS 之综合性警报,任何一个UPS 内部警报都会导致本警报之产生;当此报
警出现时,伴随有8位16进制代码,可具体查找到报警的信息。可通过报警复位对
其进行恢复。
(电池故障)
A06?:
BATTERY FAULT
POSTIL?: The battery voltage is out of tolerance. .
注释:电池电压超出范围。检查电阿池组电压,是否低于最低允许值(单只电池最低放
电电压为10.5V),如果电压低限,要及时恢复主电源供电,或将UPS负载减小。此
报警一般是长时间放电引起或是由于电池组中电池有问题。
(电池开路报警)
A07?:
BATTERY CIRCUIT OPEN FAULT
POSTIL: Batteries are not connected. The battery switch or breaker is open or the
battery fuses are broken.
注释:电池开关F1尚未投入,或电池组保险烧断。请检查电池开关及保险
(手动旁路激活)
A08?:
MANUAL BY-PASS ACTIVE
POSTIL: a)For UPS 10 to 30 kVA, the output switch Q2 is in position 2.
b)For UPS 40 and 60 kVa, the switch Q5 is closed.
注释: a)10 – 30 KVA UPS:输出开关Q2 置于2 段位置。
b)40 – 60 KVA UPS:手动旁路开关Q5 已投入。
此一情况代表负载直接由市电供电,在
报警。请不要随意闭合手动开关
UPS开机或关机及转旁路维修时会出现此
(仿真流程控制面板故障)
A09?:
MIMIC PANEL FAULT
POSTIL: The mimic panel is defective. The information displayed may be wrong. It
may be a problem with mimic panel pcb, DE pcb or the CAN BUS cable.
注释:仿真流程控制面板故障,此时显示出来的数值可能已经错误,本故障原因于PCB DE
板与仿真流程控制面板无法通讯,仿真流程控制面板、
线故障都可能引起此一警讯。出现此报警,机器正常工作
PCB DE 板故障及通讯连接
A10: PRESERVING(预留报警,未使用)
(有缘滤波器故障)
A11?:
ACTIVE FILTER ALARM
POSTIL: This alarm may be only displayed on DIGYS ?. In this case a specific alarm
code in hexadecimal is displayed (like service code), UPS is still
active filtre is off.
running but the
注释:如果整流器之输入电流谐波超过5% 即出现本警讯,此时UPS 仍然可正常工作;正
常报警,当输入谐波降低后,报警消失。
A12?: OPT2 BOARD ALARM(外部接口板故障)
POSTIL: This alarm is activated when at least one of the inputs of the dry contact
pcb (S6.839.x/04) is closed.
注释:外部接口板(选购)故障。检查标号为6839X04的PCB板
(主从不同步报警)
A13?:
INVERTER MAINS SYNCHRONIZATION FAULT
POSTIL?: Inverter and mains are not synchronized. If the alarm A03 is also active,
it means that the non synchronization is due to R2 frequency out of
tolerance.
If it’s the only active alarm, it means that R2 frequency is subject to
continuous variations. This is typical when the UPS is supplied by an
emergency generator.
注释:逆变器与市电不同步,如果同时出现
之电压或频率异常而引起的,通常当
A03 之警报,则表示本警报是因为旁路电源
UPS 由发电机供电时较容易出现这种状况。
当市电的电压或频率恢复时,报警解除,正常报警,不需要认为动作。
(风机故障)
A14?:
VENTILATION FAN FAULT
POSTIL: The UPS internal temperature is too high. The possible reasons are?:
-
One or more fans are broken.
-
The room temperature is more than 40°C.
-
There is not enough space around the UPS cabinet.
注释: UPS 内部温度过高。此报警可能由于下列原因:
一个或多个风机故障
环境温度超过40°C。
UPS 摆设位置未依照规范致使散热空间不足
(电池测试报警)
A15?:
BATTERY TEST ALARM
POSTIL: The result of the battery test is not good.
注释: UPS 将每隔一段时间执行电池放电测试以检查电池是否正常,本警报之出现代表
电池放电测试时电池放电能力不足,需要及时更新。出现此报警需检查电池组是
否还可继续使用。
(定期维护保养)
A18:
PERIODIC SERVICE CHECK UP
注释:为确保本产品之性能保持在最理想状态,定期检查及维护UPS 是必要的,假如UPS
出现A18: PERIODIC SERVICE CHECK UP 警讯时,即代表本UPS 需执行维护保养
工作。需要工程师现场服务。