admin 管理员组文章数量: 1086019
2024年2月23日发(作者:矿用z型钢)
Electrical Machines And Electrical Apparatus
1 • Construction and Principles of Power Transformer
Transformer is an indispensable component in many energy conversion systems. It makes
possible electric generation at the most economical generator voltage, power transfer at the most
economical transmission voltage, and power utilization at the most suitable voltage for the particular
utilization device. The transformer is also widely used in low-power, low-current electronic and
control circuits for performing such functions as matching the impedances of a source and its load for
maximum power transfer, isolating one circuit from another, or isolating direct current while
maintaining alternating current continuity between two circuits-
Essentially, a transformer consists of two or more windings coupled by mutual magnetic flux. If
one of these windings, the primary is connected to an alternating voltage source, an alternating flux
will be produced whose amplitude will depend on the primary voltage, the frequency of the applied
voltage, and the number of turns. The mutual flux will link the other winding, the secondary and will
induce a voltage in it whose value will depend on the number of the secondary turns as well as the
magnitude of the flux and the frequency. By properly proportioning the primary and the secondary
turns, almost any desired voltage ratio, or ratio of transformation, can be obtained.
The essence of transformer action requires only the existence of time-varying mutual flux linking
two windings. Such action can occur for two windings coupled through air, but coupling between the
windings can be made much more effectively using a core of iron or other ferromagnetic material,
because most of the flux is then confined to a definite, high-permeability path linking the windings.
Such a transformer is commonly called an iron-core transformer. Most transformers are of this type.
The following discussion is concerned almost wholly with iron-core transforme匚
In order to reduce the loss caused by eddy current in the core, the magnetic circuit usually
consists of a stack of thin laminations. Two common types of construction are shown schematically in
Fig. 1.1 • In the core type (Fig. 1.1a) the windings are wound around two legs of a rectangular
magnetic core; in the shell type() the windings are wound around the center leg of a
three-legged core. Silicon -steel laminations 0-014 mm in thick are generally used for transformer
used at frequencies below a few hundred Hz. Silicon steel has the desirable property of low cost, low
core loss, and high permeability at high flux densities (1.0 to 1.5T). The cores of small transformer
used in communication circuits at high frequencies
and low energy levels are sometimes made of compressed ferromagnetic alloys known as ferrites-
Core
—Windings
Windings
(a) (b)
In each of these configurations, most of the flux is confined to the core and therefore links both
windings. The winding also produce additional flux, known as leakage flux, which links one winding
without linking the other. Although leakage flux is small fraction of the total flux, it plays an
important role in determining the behavior of the transforme匸In practical transformers, leakage is
reduced by subdividing the windings into sections placed as close together as possible. In the
core-type construction, each winding consists of two sections, one section on each of the two legs of
the core, the primary and secondary windings being concentric coils. In the shell type construction,
variations of the concentric-winding arrangement maybe used, or the windings may consist of a
number of thin pancake coils assembled in a stack with primary and secondary coils interleaved.
2. Advantages of Balanced Three-phase Versus Single-phase Systems
In both transformers and rotating machines, a magnetic field is created by the combined action of
the currents in the windings. In an iron-core transformer, most of this flux is confined to the core and
links all the windings. This resultant mutual flux induces voltages in the windings proportional to their
number of their turns and is responsible for the voltage-changing property of a transformer. In rotating
machines, the situation is similar, although there is an air gap which separates the rotating and
stationary components of the machine. Directly analogous to the manner in which transformer core
flux links the various windings on a transformer core, the mutual flux in rotating machines crosses the
air gap, linking the windings on the rotor and stator. As in a transformer, the mutual flux induces
voltage in these winding proportional to the number of turns and time rate of change of the flux.
A significant difference between transformers and rotating machines is that in rotating machines
there is relative motion between the windings on the rotor and stator. This relative motion produces an
additional component of the time rate of change of the various winding flux linkages. The resultant
voltage component, known as the speed voltage, is characteristics of the process of electromechanical
energy conversion. In a static transformer, however, the time variation of flux linkages is caused
simply by the time variation of winding current; no mechanic motion is involved, and no
electromechanical energy conversion takes place.
The resultant core flux in a transformer induces a counter Electro-Motive Force(EMF) in the
primary which, together with the primary resistance and leakage-reactance voltage drops, must
balance the applied voltage. Since the resistance and leakage -reactance voltage drops usually are
small, the counter EMF must approximately equal to the applied voltage and the core flux adjust itself
accordingly. Exactly similar phenomena must take place in the armature windings of an AC motor.
The resultant air-flux wave must adjust itself to generate a counter EMF approximately equal to the
applied voltage. In both transformers and rotating machines, the Magneto-Motive Force (MMF) of all
the currents must accordingly adjust itself to create the resultant flux required by this voltage balance.
In any AC electromagnetic devices in which the resistance and leakage-reactance voltage drops are
small, the resultant flux is very nearly determined by the applied voltage and frequency, and the
cuiTents must adjust themselves accordingly to produce the MMF required to create this flux.
In a transformer, the secondary current is determined by the voltage reduced by the secondary
winding, the secondary leakage impedance, and the electric load. In an induction motor, the
secondary(rotor) current is determined by the voltage induced in the secondary, the secondary leakage
impedance, and mechanical load on its shaft. Essentially the same phenomena place in the primary
winding of the transformer and in the armature (stator) windings of induction and synchronous motors.
In all three, the primary, or armature, current must adjust itself so that the combined MMF of all
currents creates the flux the required by the applied voltage.
In addition to the useful mutual fluxes, in both transformers and rotating machines there are
leakage fluxes which link individual windings without linking others. Although the detailed picture of
the leakage fluxes in rotating machines is more complicated than that in transformers, their effects are
essentially the same. In both, the leakage fluxes induce voltage in AC windings which are accounted
for as leakage-reactance voltage drops. In both, the reluctances of the leakage-flux paths are
dominated by that of a path through air, and hence the leakage fluxes are
nearly linearly proportional to the current producing them・ The leakage-reactance therefore is often
assumed to be constant, independent of the degree of saturation of the main magnetic circuit.
Further examples of the basic similarities between transformer and rotating machines can be
cited. Except for friction and windage, the losses in transformer and rotating machines are essentially
the same. Tests for determining the losses and equivalent circuit parameters are similar: an open
circuit, or no-load, test gives information regarding the excitation requirements and core losses(along
with friction and windage losses in rotating machines), while a short-circuit test together with DC
resistance measurements gives information regarding leakage reactance and winding resistances.
3. Elementary Knowledge of Rotating Machines
Electromagnetic energy conversion occurs when changes in the flux linkage result from
mechanical motion. In rotating machines, voltage are generated in windings or groups of coils by
rotating these windings mechanically through a magnetic field, by mechanically rotating a magnetic
field past the winding, or by designing the circuit so that the reluctance varies with rotation of the
motor. By any of these methods, the flux linking a specific coil is changed cyclically, and a
time-varying is generated.
A set of such coils connected together is typically referred to an armature winding. In general,
the term armature winding is used to refer to a winding or a set of windings on a rotating machine
which carry AC currents. In AC machines such as synchronous or induction machines, the armature
winding is typically on the stationary portion of the motor refeiTed to as the stator, in which case
these windings may also be referred to as stator windings.
In a DC machine, the armature winding is found on the rotating member, referred to as the rotor.
The armature winding of a DC machine consists of many coils connected together to form a closed
loop. A rotating mechanical contact is used to supply current to the armature winding as the rotor
rotates.
Synchronous and DC machine typically include a second winding (or set of settings) which carry
DC current and which are used to produce the main operating flux in the machine. Such a winding is
typically refeiTed to as field winding. The field winding on a DC machine is found on the stator,
while that on a synchronous machine is found on the rotor, in which case current must be supplied to
the field winding via a rotating mechanical contact. As we have seen, permanent magnetic also
produce DC magnetic flux and are used in the place of field windings in some machines.
In most rotating machines, the stator and rotor are made of electrical steel, and the windings are
installed in slots on these structures. The use of such high-permeability material maximizes the
coupling between the coils and increase the magnetic energy density associated with the interaction.
It also enables the machine designer to shape and distribute the magnetic fields according to the
requirements of each particular machine design. The time varying flux present in the armature
structures of these machines tends to induce cuiTents, known as eddy currents, in the electrical steeL
Eddy currents can be a large source of loss in such machine and can significantly reduce machine
performance. In order to minimize the effects of eddy currents, the armature structure is typically
built from thin laminations of electrical steel with are insulated from each other.
In some machines, such as reluctance machines and stepper motors, there are no windings on the
roton Operation of these machines depends on the nonuniformity of air-gap reluctance associated
with variations in rotor position in conjunction with time-varying currents applied to their stator
windings. In such machines, both the stator and rotor structures are subjected to time-varying
magnetic flux and, as a result, both may require lamination to reduce eddy-current losses.
Rotating electric machines take many forms and are known by many names: DC, synchronous,
permanent-magnet, induction, variable reluctance, hysteresis, brushless, and so on. Although these
machines appear to be quite dissimilar, the physical principles governing their behavior are quite
similar, and it is often helpful to think of them in the same physical picture.
版权声明:本文标题:关于潮流计算外文文献原文x 内容由网友自发贡献,该文观点仅代表作者本人, 转载请联系作者并注明出处:http://www.roclinux.cn/b/1708669078a528978.html, 本站仅提供信息存储空间服务,不拥有所有权,不承担相关法律责任。如发现本站有涉嫌抄袭侵权/违法违规的内容,一经查实,本站将立刻删除。
发表评论